logo delle turbine capstone

La turbina a gas oil-free da 200 kWe

La turbina Capstone C200 da 200kWe rappresenta il turbogeneratore oil-free più evoluto al mondo per l’autogenerazione ad alta efficienza di energia elettrica e termica.

HIGH-PRESSURE NATURAL GAS

World’s largest air-bearing microturbine produces 200kW of clean, green, and reliable power

  • Ultra-low emissions
  • One moving part – minimal maintenance and downtime
  • Patented air bearings – no lubricating oil or coolant
  • 5 and 9 year Factory Protection Plans available
  • Remote monitoring and diagnostic capabilities
  • Integrated utility synchronization and protection
  • Small, modular design allows for easy, low-cost installation
  • Proven technology with tens of millions of run hours and counting
  • Internal fuel gas compressor available for low fuel pressure natural gas applications

  • Electrical Power Output: 200kW
  • Voltage: 400/480 VAC
  • Electrical Service: 3-Phase, 4 Wire
  • Frequency: 50/60 Hz, grid connect operation | 10– 60 Hz, stand alone operation
  • Maximum Output Current: 290A RMS @ 400V, grid connect operation | 240A RMS @ 480V, grid connect operation | 310A RMS, stand alone operation(2)
  • Electrical Efficiency LHV: 33%
  • Natural Gas HHV: 30.7– 47.5 MJ/m3 (825–1,275 BTU/scf)
  • Inlet Pressure: 517– 552 kPa gauge (75– 80 psig)
  • Fuel Flow HHV: 2,400 MJ/hr (2,280,000 BTU/hr)
  • Net Heat Rate LHV: 10.9 MJ/kWh (10,300 BTU/kWh)
  • NOx Emissions @ 15% O2: < 9 ppmvd (18 mg/m3 )
  • NOx / Electrical Output(4): 0.14 g/bhp-hr (0.4 lb/MWhe)
  • Exhaust Gas Flow: 1.3 kg/s (2.9 lbm/s)
  • Exhaust Gas Temperature: 280°C (535°F)
  • Exhaust Energy: 1,420 MJ/hr (1,350,000 BTU/hr)
  • Width x Depth x Height(6): 1.7 x 3.8 x 2.5 m (67 x 150 x 98 in)
  • Weight – Grid Connect Model: 2776 kg (6,120 lb)
  • Weight – Dual Mode Model: 3413 kg (7,525 lb)
  • Vertical Clearance: 0.6 m (24 in)
  • Horizontal Clearance
    • Left & Right: 1.1 m (42 in)
    • Front: 1.1 m (42 in)
    • Rear: 1.8 m (70 in)

Acoustic Emissions at Full Load Power
Nominal at 10 m (33 ft): 65 dBA

  • UL 2200 and UL 1741 natural gas operation(8)
  • Complies with IEEE 1547 and meets statewide utility interconnection requirements for California Rule 21 and the New York State Public Service Commission
  • CE certified

CASI STUDIO